- Order number: 801620-01
+49 (0) 8405 / 9259-0 | |
Contact us via email |
With this active and thermoelectric cooling system you can call up a cooling capacity of up to 100 W at ΔT 0K. The cooling system is a powerful liquid cooling and temperature control system in compact size, with all cooling system components integrated within the housing.
The cooling system tempers the cooling water to room temperature against the power loss introduced from outside via the cooling circuit. The system can be filled quickly and easily thanks to the large filler neck in the lid of the cooling system. The EHEIM pump installed in the system ensures a continuous and safe coolant flow.
All connections and terminals for power supply etc. are located on one side of the unit for easy access. The coolant connections are equipped with drip-free CPC-NS2 couplings (female), so that the system can be quickly and safely connected to the cooling circuit. Integrated air filters also protect the system from dust loads.
The integrated microcontroller control system monitors and controls the entire cooling system. In addition, a programmable fault alarm is available on the system interface. The integrated status LEDs also indicate proper operation or a possible error visually on the device.
Note: This cooling system is produced explicitly on customer request. Once we have received your paid order, you will be informed of the estimated production time. After your approval, the production will be carried out and the cooling system will be dispatched to you after completion.
Technical details:
Type: | Active cooling system (with Peltier) |
Dimensions: | 385 x 250 x 250 mm (LxBxH) |
Weight: | ca. 14 kg (unbefüllt) |
Loudness: | ~ 46 dB(A) |
Fan: | 2x 80 x 80 x 25 mm (12 V, 3 W) |
Ambient temperature: | 10 °C bis 35 °C |
Cooling water temperature: | max. 60 °C |
Prescribed coolant: | innovatek Protect IP (25 % Protect IP, 75 % destilliertes Wasser) |
Tank volume: | 2 l |
Cooling capacity: | 100 W (bei ΔT 0K) |
Delivery rate (external): | max. 5 l/min |
Supply pressure (external): | 0,7 bar |
Voltage Range: | 24 V DC |
Power consumption: | max. 200 Watt (10 A) |
Connector: | Forward and reverse: CPC-NS2 coupling (hydraulic, female) |
Electrical interface: | Steckverbinder Hirschmann CA-Serie Nennstrom: 10 A/AC/DC Pole: 6 + PE Typ 932 326-100 |
Miscellaneous: | Automatisches Entlüftungssystem Luftfilter G2 Selbstsperrende Ablasskupplung Niveausensor im Tank Füllstandsüberwachung mit Signalausgang |